Eaton CEAG DualGuard-S Mounting And Operating Instructions page 127

Table of Contents

Advertisement

Technical description
Dimensions (W x H x D):
Colour:
Weight:
Assembly:
Degree of protection:
Protection class:
Ambient temperature:
Degree of pollution:
Electromagnetic compatibility:
Rated voltage (Mains):
Rated current (Mains):
Rated voltage (Battery):
Rated current (Battery):
Rated Frequency:
Overvoltage category:
Max. connected load:
Maximum numbers of modules:
Controller ACU DG / HMI
PSU
SKU.1.1 CG-S:
1x6A
2x3A
4x1,5A
Max. numbers luminaire circuits:
Terminals:
ACU DG
Luminaire circuits
Battery feed
Battery through-wiring
Mains feed
Mains through-wiring
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
600x400x300 mm
RAL 7035
42 kg
Recommended for wall mounting: 4xM8 (min.
2xM8)
Force [N]: 1861
Mounting stability [N]: 950
IP54
I
-5°C to +35°C
2
Industry EN 61000-6-2, Commercial EN 61000-6-3
UN = 230 V AC
IN = 30 A
216 V DC
IN =30 A
50 or 60 Hz
Mains: III / Battery: II
At +35°C < 6,5 KW
1
1
0-7
0-7
0-7
28
2,5mm² Rigid/ 1,5mm² flexible
4 mm² Rigid/flexible
16 mm² Rigid/flexible
16 mm² Rigid/flexible
16 mm² Rigid/flexible
16 mm² Rigid/flexible
50 DualGuard-S US 7
Field
A4
A4
A1
B1
A3
A3
A1
A3
A4
A4
A4
A4
127