Eaton CEAG DualGuard-S Mounting And Operating Instructions page 77

Table of Contents

Advertisement

Technical description
Dimensions (W x H x D):
Colour:
Weight:
Assembly:
Degree of protection:
Protection class:
Ambient temperature:
Degree of pollution:
Electromagnetic compatibility:
Rated voltage (Mains):
Rated current (Mains):
Rated voltage (Battery):
Rated current (Battery):
Rated Frequency:
Overvoltage category:
Max. connected load:
Maximum numbers of modules:
Controller ACU DG / HMI:
PSU:
BCM.1:
SKU.1.1 CG-S:
1x6A
2x3A
4x1,5A
Luminaire circuits:
Charger CM 1,7A
Charger CM 3,4A
Battery/mains distribution
Terminals:
Luminaire circuits:
BCM.1:
ACU DG
Battery feed:
Battery distribution:
Mains feed:
Mains distribution board:
Order number accesories:
Cupboard base 100mm
Cupboard base 200mm
Door hinge left
Special locking profile half cylinder
IP 31 Retrofit kit
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
2070 x 800 x 405 mm
RAL 7035
180 kg
Only set up on non-combustible ground (e.g. con-
crete).
IP21, optional IP31, on request IP54
I
-5°C to +35°C
2
Industry EN 61000-6-2, Commercial EN 61000-6-3
UN = 400/230 V AC
IN = 80 A
216 V DC
IN =80 A
50 or 60 Hz
Mains: III / Battery: II
At +35°C < 17 ,3 KW
1/1
1-2
1
0-28
0-28
0-20
0-88
1-2
0-8
0-6
4 mm² Rigid/flexible
4 mm² Rigid/flexible
2,5mm² Rigid/ 1,5mm² flexible
50 mm² Rigid/flexible
16 mm² Rigid/flexible
50 mm² Rigid/flexible
16 mm² Rigid/flexible
40071362282
40071362283
40071362301
40037079790
40071362291
36 DualGuard-S 28
Field
Â1
B1-C1
B2
B3-E
B3
H1-4
F-G
A2-4
A2
A1
F1
F2
G1
G2
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents