Dualguard-S Esf30 Us Sou1 - Eaton CEAG DualGuard-S Mounting And Operating Instructions

Table of Contents

Advertisement

58 DualGuard-S ESF30 US SOU1

The DualGuard-S ESF30 US SOU1 sub-station in accordance
with EN 50171 supplies 230V / 216V AC/DC safety and
escape sign luminaires and is particularly suitable for instal-
lation in fire compartments in buildings with a large number
of fire compartments. Thus, the decentralised design of the
system can contribute to reducing the costs for function
maintenance cabling. The automatic test device and indivi-
dual luminaire monitoring with individual status and name
indication per luminaire in conjunction with system-related
ECG / LED supply module including monitoring module
without additional data line reports and proclaims the ope-
rating states.
Consisting of:
Fire protection wall distributor with cable entry from above
and a SOU CG-S 2x4A circuit changeover.
Technical description
Dimensions (W x H x D):
Colour:
Weight:
Assembly:
Degree of protection:
Protection class:
Ambient temperature:
Degree of pollution:
Electromagnetic compatibility:
Rated voltage (Mains):
Rated current (Mains):
Rated voltage (Battery):
Rated current (Battery):
Rated Frequency:
Overvoltage category:
Max. connected load:
Maximum numbers of modules:
SOU CG-S 2x4A
Luminaire circuits:
Terminals:
Luminaire circuits:
Battery feed:
Battery through-wiring:
Mains feed:
Mains through-wiring:
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
540x400x230 mm
RAL 7035
34 kg
Wand
IP65
II Schutzisoliert nach VDE 0106
-5°C to +35°C
2
Industry EN 61000-6-2, Commercial EN 61000-6-3
UN = 230V AC
IN = 5 A
216 V DC
IN =5 A
50 or 60 Hz
Mains: III / Battery: II
At +35°C < 1,1 KW
1
2
4 mm² Rigid/flexible
10 mm² Rigid/flexible
10 mm² Rigid/flexible
10 mm² Rigid/flexible
10 mm² Rigid/flexible
58 DualGuard-S ESF30 US SOU1
1
2
Field
A1
A1
A
A4
A2
A2
A3
A3
3
4
A
B
396
C
D
135