Eaton CEAG DualGuard-S Mounting And Operating Instructions page 84

Table of Contents

Advertisement

40 DualGuard-S LAD 100
23,3 Ah Battery wiring standing cabinet
Technical description
Battery type (C10; 1,8 V/Z; +20 °C):
Nominal battery voltage of all connected
cells
Numbers of battery blocks:
Dimensions per block in mm (L x W x H): 168 x 127 x 174
End poles
Order Number battery block:
Dimensions Battery cabinet
in mm (B x H x D):
Battery consoles:
Terminals:
Weight incl. Batterys:
Degree of protection:
Order Number wiring set:
15 x Length 1:
2 x Length 2:
1 x Length 3:
1 x Length 4:
32 Ah Battery wiring standing cabinet
Technical description
Battery type (C10; 1,8 V/Z; +20 °C):
Nominal battery voltage of all connected
cells
Numbers of battery blocks:
Dimensions per block in mm (L x W x H): 198 x 168 x 175
End poles
Order Number battery block:
Dimensions Battery cabinet
in mm (B x H x D):
Battery consoles:
Terminals:
Weight incl. Batterys:
Degree of protection:
Order Number wiring set:
15 x Length 1:
2 x Length 2:
1 x Length 3:
1 x Length 4:
84
Mounting- and Operating Instruction CEAG DualGuard-S 40071860347 January 2020 www.ceag.de
12 V / 23,3 Ah
216 V
18 á 12 V
M6
40066070461
800 x 2050 x 400
3
max. 35 mm²
295 kg
IP21
40071346779
300 mm
1000 mm
800 mm
2000 mm
12 V / 32 Ah
216 V
18 á 12 V
M6
40066070116
800 x 2050 x 400
3
max. 35 mm²
370 kg
IP21
40071346779
300 mm
1000 mm
800 mm
2000 mm
3
4
1
1. Battery console
2
2. Battery console
3. Battery console
3
4
1. Battery console
2
2. Battery console
3. Battery console
1