Commissioning DFA 127

13.1

Principles of commissioning

13.1.1

Requirements of the technician

The technician must know the functions and the operation of service and flash-programmer
FPC and control unit BDE-D exactly.
13.1.2

Mechanical final test

Manually check the following points:
▪ Manually opening the of door over the whole sliding length
▪ No abnormal sounds are audible
▪ All screws are tightened
▪ Locking device control:
– Bolt engages correctly with straps
– Is there enough clearance available?
▪ Casing is properly positioned
13.1.3

Wiring control

▪ All terminal blocks are tightened
▪ All cables are properly fastened, so that they are not damaged by the carriages or the
toothed belt.
13.1.4

Checking safety devices

New installations must comply with standard EN 16005 to its full extent. The commissioning
of a door must occur together with the operator of the door, and the latter must approve all
the functions of the door.
Currently existing installations must be inspected carefully during the official service, and the
customer should be encouraged to bring their door into line with standard EN 16005 with re-
gard to safety by means of a risk assessment if necessary.
▪ Countries where standard DIN 18650 is still valid:
„Risk assessment according to machinery directives in reference to DIN 18650 STA" –
Check all the points listed in that document and make the customer sign it. A copy is
handed over to the customer.
Moreover, the following functions - if applicable and not already covered by the hazard
analysis mentioned above - have to be checked:
▪ Automatic reverse - in both directions (closing and opening)
▪ Trouble-free operating of manual unlocking device (if available)
▪ Emergency opening switch (if available) - Door must open - automatic reverse is en-
abled. However, door stays closed during operating mode „
102-127108955
Commissioning DFA 127
V1.1
Locked"