Record DFA127 Instructions Manual page 62

Automatic door systems
Hide thumbs Also See for DFA127:
Table of Contents

Advertisement

TIME DELAYS OPEN
→ Time delay SSK
DRIVE
→ Opening angle
→ Collision CLOSED
→ Collision OPEN
102-127108955
21..40 = 22 to 60 seconds, 2 s increments
▪ The hold-open time starts only after all trigger and
4
Determines the minimum time for which a door stays open
after it has been opened by a type SSK triggering signal.
0..20 = 0 to 20 seconds, 1 s increments
21..40 = 22 to 60 seconds, 2 s increments
▪ The hold-open time starts only after all trigger and
NOTICE
The open duration can be reduced when sensors are used which keep the door
Time delay
open, for example,
35
The opening angle is read during the learning cycle and corre-
sponds to the value 40.
0 = minimum opening angle
40 = maximum opening angle
▪ DIN: min. 95°
20
Reaction point for collision detection during closing of the door.
0 = smooth
40 = rough
▪ The kinetic energy of the moving door is partially ab-
20
Reaction point for a collision detection during opening run (se-
condary closing edge).
0 = smooth
40 = rough
▪ The kinetic energy of the moving door is partially ab-
safety signals have been made in the closing direc-
tion.
safety signals have been made in the closing direc-
tion.
with record sensors.
sorbed by the obstacle. According to its characteris-
tics, it takes a certain time for the controller to notice
the increase in force and reopen the door.
sorbed by the obstacle. According to its characteris-
tics, it takes a certain time for the controller to notice
the increase in force and stop the door.
V1.1
Configurations
16
62/ 102