Record DFA127 Instructions Manual page 70

Automatic door systems
Hide thumbs Also See for DFA127:
Table of Contents

Advertisement

→ Opening sequence
→ Closing sequence
MANUAL MODE
→ When closing
→ Disabled
→ Active
102-127108955
When closing, the moving leaf waits until the stationary leaf is
closed.
▪ With low door thickness and slight overlap, the value
5
Delayed approach to stationary leaf.
0 = no delay
40 = max. delay (moving leaf opens completely)
20
Delayed closure of the moving leaf.
0 = no delay
40 = max. delay (stationary wing closes completely)
NOTICE
All controls to 0 = synchronous mode.
Opening or closing sequence to 40: The following door leaf waits until the first
door leaf is fully open or fully closed. With these settings, the overlap has the
highest priority.
The parameter defines how the door is to react in the operat-
ing mode
▪ With low-energy applications the door closes in 'Ma-
X
The door closes with motor drive and programmed closing
speed.
The door closes with motor drive controlled only by spring
tension.
▪ When using drives on fire-resistant doors the closing
of 2 can be adjusted to achieve a continuous closing
process.
'Manual'
.
nual mode'.
time for the event of a power failure or a drive failure,
according to the table in the chapter Fire Protection
Specification, must be set by means of jumper J5 to
motorprint MOT.
V1.1
Configurations
16
70/ 102