Illustration 5.2: Configuring Active Power Control – PLA
To proceed with the configuration guide, press 'Next'.
5.3.1. Configuring Reactive Power Control – Percent of Q (TLX Pro
+ only)
Set the 'Remotely controlled reactive power (Q)' radio button. Configure the relay states (K1–
K4) according to the requirements of the DNO by entering the appropriate reactive power set
point of Q for each relay state specified by the DNO. The value entered is set on each inverter
and represents the amount of reactive power that the inverter will deliver. Leave Q settle time
at 10 s, unless otherwise specified by the DNO.
Note:
Q values can also be entered as absolute values by changing the unit using the drop-down
box.
L00410637-01_02