How To Change Access Levels Of 'Buzzer' & 'Device Disablement; How To Change The 'Alarm Controls' Settings - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

Commissioning instructions
How to change access levels of 'Buzzer' & 'Device Disablement'
By default the buzzer can be cancelled at access level 2 and devices plus interface channels can be disabled at access level 3. It is possible to change the access levels of these controls, however you
will need to be at access levels 3 or above to make these changes.
Menu
Settings
Select
System >
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.

How to change the 'Alarm Controls' settings

After alarms have been silenced during or following a fire condtion the same alarms can be activated again by pressing the 'Sound Alarms' button, providing the 'Resound' mode is configured. In the
same scenario if configured for 'Sound' mode and on pressing the 'Sound alarms' button it will activate all the sector alarms. The Fire relay can be configured to be active with the 'Sound alarms' button.
You will need to be at access level 3 or above to change 'Sound alarms' button settings.
Menu
Select
Settings
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
58
Select
Select
More
>
Select
Alarms
>
Controls
The 'Cancel buzzer' function can be either at Access level 1 [1] or at Access Level 2 [2](factory default setting)
Access Level Settings
Cancel Buzzer Level : [2]
Access Levels
Select
Disablement Level
The ability to disable devices can be at level 3 [3] (Factory default setting) or at Access level 2 [2]
10:15 Tue 16/02/10
Sound Alarms Settings
Sound Alarms Mode : [RESOUND]
New Fire Resounds Alarms : [NO ]
Select
Sound Alarms Operates Fire Relay
Save
To move to the
To scroll the
range
next setting
10:15 Tue 16/02/10
Save
:
[3]
Save
Quit
Set Sound Alarm mode to 'SOUND' or
'RESOUND' (Factory default setting).
New Fire to resound alarms of previous
fire events as well 'Yes' or 'NO'
Factory default setting)
[NO]
Set 'Sound alarm' to operate Fire relay:
Quit
'NO' Factory default setting) or 'YES'
Save
To scroll the
range
4188-949 issue 3_05/10_Nano Comms inst.
To move to
next setting