Commissioning instructions

Factory default settings

The list below provides information on how the panel is configured on leaving the factory:

Devices

¨
All Sensor Devices are assigned to Zone 1
¨
All Sounder/Output Devices are assigned to Sector 1
¨
All Devices operate sensitivity state 0 in both Day and Night mode, where applicable
¨
All Device labels are 'Device n', where n signify the device number
¨
All Single channel interface devices are configured as zone inputs
¨
All 4 channel interface devices are configured as LED outputs

Modes of operation

¨
The panel will operate in Night mode
¨
All Sectors are in ALARM mode, not PLANT mode
¨
All Sectors activate by Class Change input
¨
Sound Alarm button operates in 'RESOUND mode' without the Fire Relay

Access levels

¨
Access level 1 - no code required
¨
Access level 2 (Customer mode) - 0 0 0 0
¨
Access level 3 (Engineering mode) - 3 3 3 3
¨
Access level 4 (Maintenance mode) - 4 4 4 4

External circuits

¨
External Evacuate input - Not configured for use
¨
Class change input - Not configured for use
¨
RS-232 port - Enabled for PRINTER connection
¨
RS-485 port - Local repeat panel - Not configured for use
¨
USB port - for COMMISSIONING TOOL use
10

Zones

¨
All Zones - in Normal mode (not in 2-detector mode nor in 2 -zone mode)
¨
All Zone labels are 'Zone n' where n signify the zone number
¨
All Zones are independent - not linked to another zone
¨
Only Zone 1 is Enabled, Zone 2 to 16 are disabled
¨
No Zones are in Test mode

Immediate Cause and Effect

¨
All zones will action 'no action' on all Sectors
¨
All zones are configured for 'no action' on Master alarms
¨
All zones are configured for 'no action' on Fire relay activation

Day mode delay

¨
Initial delay is 30 seconds
¨
Day mode delay is 5 minutes
¨
Day mode timeout is 8 hours
¨
Manual mode (not in On, Off or Calender mode)

Delayed Cause and Effect

¨
All zones will action Evacuate alarms on all Sectors after a delay
¨
All zones will action Master alarms after delay
¨
All zones will action Fire relay after delay