How to set up RS-232 and RS-485 serial and USB ports

The RS232 port is used to connect an external printer to the control panel for printing active events and loop map. The RS485 port allows up to 4 repeat indicator panels to be connected to the control
panel for repeat indication and messages of system events. Note some messages displayed at the repeat indicator panel are worded slightly different but they mean exactly the same, see Appendix C.
The USB port is for the Commissioning tool. You will need to be at access level 3 or above to set-up the serial ports.
Menu
Settings
Select
System >
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
REPEAT INDICATOR PANEL
If there is only one repeat indicator panel
connected then it is possible to use the 24V
supply on the Main control board.
4188-949 issue 3_05/10_Nano Comms inst.
Select
More
>
Select
Thermal printer
9-way D-type
b
connector
RS485
a
+
24V
-
earth
B
A
DRN
24V 0V
RS485
PP3
MAIN CONTROL BOARD
PANEL
Serial Port Settings
RS232 Status
Serial Ports
Select
RS485 Local Repeat : [NOT FITTED]
USB Function
Save
Select USB function for:
'VigTool
'COMMTOOL' (factory default setting)
'PRINTER'
5
3
2
0V
RX TX
DRN
ISO
ISOLATED RS232
PP10
MAIN CONTROL BOARD
PANEL
The panel's RS-232 port is set at 9600 baud.
Nano panel based system
Save
10:15 Tue 16/02/10
:[PRINTER]
Select RS232 status -
'PRINTER' (Factory default setting)
'DISABLED'
:[COMMTOOL]
'TEST'
Quit
Select if RS485 port is in use with
Repeat indicator panel if fitted-
'REPEAT' or 'DISABLED' (Factory default setting)
To move to
To scroll the
next setting
range