How To Set-Up The 'Class Change Input - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

Commissioning instructions

How to set-up the 'Class Change input'

The class change input application is used in schools to output a class change alarm via the sounders in selected sectors to signify end of class.
You will need to be at access level 3 or above to configure class change input.
Menu
Settings
Select
System >
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
You will also need to assign class change to activate sectors see section headed 'How to set-up 'Sector' mode, label and activation'.
Class Change
Switch
Normally open contacts
2 - 10K Ohms -
resistors must be
fitted as shown.
+VE
0V
DRN
CLASS CHANGE
PP8
12:30 Tue 16/02/10
Nano Fire Alarm System
Gent by Honeywell
[MENU]
Cancel
Sound
Silence
Buzzer
Reset
Alarms
Alarms
Disablement
Test
Delay
Verify
Sounder
System Fault
Power Fault
Sounder Fault
Disablement
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 16
Zone 13
Zone 14
Zone 15
FAULT
POWER
FIRE
042bc
by Honeywell
EN54 Parts 2 & 4
56
Select
More
>
Select
CLASS CHANGE ALARM
External Inputs
Select
To stop the class change alarms
simply release the switch.
10:15 Tue 16/02/10
External Input Settings
External Evacuate Input Used
: [NO ]
External Evacuate Input Latches : [NO ]
Class Change Input Used
: [NO ]
Save
Save
Quit
Set the 'Class Change' input
use requirement to - 'NO' (factory default setting) or 'YES'
To move to the
To scroll the
settings
class change
field
4188-949 issue 3_05/10_Nano Comms inst.