Speech circuit has failed
Strobe circuit has failed
Too many devices on loop
76
Message
meaning..
There is a hardware fault possibly associated with the voice
chip on the speech S-Cube or S-Quad
The strobe circuit on the S-Quad or S-Cube device has
failed.
The user has attempted to connect more than the permitted
127 devices to the loop.
..possible action
Replace the device
Replace the device
Ensure that only 127 devices are connected.