A S-Quad fire sensor or manual call point will operate its LED for 0.5 second On and 0.5 second Off repeated.
Sounders and S Cubed
¨
Each S cubed or S-Quad with sounder device will provide an audible tone and/or visual indication for 0.5 second On and 0.5 second Off repeated. If the device operates in voice
mode then the pre-tone followed by a full test message will be played.
Interface units
&
Ensure Interface outputs are not connected to external equipment at this stage of commissioning. These must be tested in accordance with project
recommendations.
¨
Each interface output will in turn be activated for 0.5 second On and 0.5 second Off, this will repeat.
How to 'Print' the Loop map
You can print the loop map to a local printer connected to the panel. You will need to be at access level 4.
"
A printout will only print the first 15 characters of a label due to the limit of 40 characters per line on the handheld printer.