How To Set Up An 'External Evacuate Input - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

How to set up an 'External Evacuate input'

The External evacuate input operates in the same way as the Sound/Silence buttons. The input can be set as a latched or non latched input.
You will need to be at access level 3 or above to set up the external evacuate input.
Menu
Settings
Select
System >
After making changes to this form you will need to back-up the data to
memory. Ensure the write protect link P9 on the MCB is configured in
the ENABLED position to allow back-up of data.
Evacuation Input
O
Switch
I
Normal
Normally open contacts
O
I
Active
2 - 10K Ohms -
resistors must be
fitted as shown.
FIRE
+VE
0V
DRN
Common fire LED
(Flashing indication)
red LED
EXT.EVAC.
PP8
12:30 Tue 16/02/10
Nano Fire Alarm System
Gent by Honeywell
[MENU]
Cancel
Sound
Silence
Buzzer
Reset
Alarms
Alarms
Disablement
Test
Delay
Verify
System Fault
Power Fault
Sounder Fault
Sounder
Disablement
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
Zone 9
Zone 10
Zone 11
Zone 12
Zone 13
Zone 14
Zone 15
Zone 16
FAULT
POWER
FIRE
by Honeywell
EN54 Parts 2 & 4
042bc
4188-949 issue 3_05/10_Nano Comms inst.
Select
More
>
Select
Audible
Buzzer
External Inputs
Select
The enabled ALARM sectors are activated. No
PLANT sectors will be activated.
If set up as non latching then when the input
returns to normal the system will automatically
silence.
If set up as latching then when the input returns
to normal the system will silence on Silence
Alarms.
Manually silencing the system while the external
evacuate input is active will cause a fault to be
raised until the input is cleared.
Nano panel based system
10:15 Tue 16/02/10
External Input Settings
External Evacuate Input Used
: [NO ]
External Evacuate Input Latehes
: [NO]
Class Change Input Used
: [NO ]
Save
Save
Quit
Set the 'External Evacuate' input
use requirement - 'NO' (factory default setting) or 'YES'
To scroll the
To move to
External evacuate
settings
input field