Commissioning instructions

How to conduct a 'Display Test'

It is possible to check if all the LEDS and the display of the panel have not failed by conducting a display test. You will need to be at Access Level 2 or above to conduct a Display test.
Menu
Select
User
System

How to view the panel 'Firmware'

To check you have the latest panel firmware to support the installed system you can view the firmware of the Main Controller, Loop driver and PSU.
You will need to be at Access Level 2 or above to check the panel firmware.
Menu
Engineering
>
Select

How to view the 'Historic' events log

The Historic events log holds up to 999 records of events in the system. You can scroll through all the events with event number 1 being the latest event. You can also print a range of events to a printer,
providing a printer is connected to the panel.
Menu
Logs
Historic
Select
22
Select
Display Test
>
System
>
Select
Select
Versions
>
Select
View
Print
The 'Print' option is only valid at
Access Level 2 or higher and
only when a printer is connected
to the panel.
Select
Select
Select
Firmware
Event Log (200)
1:
Zone Disabled
Zn 001:Zone 1
Select
Select
Print Event Log (200)
First Event To Print [001]
Last Event To Print
[005]
Print
Test duration is
approximately
8 seconds.
[red LEDs]
[amber LEDs]
FAULT
POWER
[amber LED]
[green LED]
10:15 Mon 15/02/10
Firmware Version Numbers
Main Controller
V2.XX
xx-xx-10
Select
Select
Loop Driver
V1.03
15-02-09
Vig Compact PSU
V2.05
01-07-08
6:15 Mon 15/02/10
10:37:20 Sun 14/02/10
Quit
To view other historic events
Quit
10:15 Mon 15/02/10
Print
Quit
To scroll the
range
4188-949 issue 3_05/10_Nano Comms inst.
Audible
FIRE
Buzzer
[red LED]