How To 'Enable' Or 'Disable' A Zone; How To Place A Zone In 'Test Mode - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

How to 'Enable' or 'Disable' a Zone

You can manually disable a zone to prevent system going into a fire condition in the event of a fire being detected in the zone. ~You can reenable the disabled zone at anytime. You will need to be at
Access level 2 or above
Menu
User
Select

How to place a Zone in 'Test Mode'

The Zone 'Test mode' function is used when testing devices in a zone. It allows the engineer to test zones without having to return to the panel to silence alarms and reset.
While the panel is in the Zone Test mode and following a fire event the alarm sounds for 5 seconds and then automatically performs the silence alarm sequence and thereafter a panel reset. The panel
inhibits the operation of delays and fire relay. For information on how to conduct a fire test see page 60.
¨
All zones of the system that are not in test mode will operate normally.
"
On completion of all commissioning work, switch Off the Zone Test mode and notice the Test indicator also switches Off.
Menu
User
Select
4188-949 issue 3_05/10_Nano Comms inst.
Zones
Select
Zones
Select
Select
Select a 'Zone' from a range 1 to 16
10:15 Tue 16/02/10
Zone : [01]
Label: Zone Label
Status : [ ENABLED ]
Test : [ NO ]
Save
Quit
Select a 'Zone' from a range 1 to 16
10:15 Tue 16/02/10
Zone : [01]
Label: Zone Label
Status : [ ENABLED ]
Test : [ NO ]
Save
Quit
Place the 'Zone' in to 'Test mode' - NO (factory default setting) or YES
Nano panel based system
To move to
To scroll the
the next setting
Save
range
Select the 'Zone' status:
Zone 'ENABLED' (factory default setting)
or Zone 'DISABLED'
Disablement
[amber LED]
To move to
To scroll the
the next setting
Save
range
Only the ALARM sectors are
actioned in Test, the PLANT
sectors are not affected.
Test
[amber LED]
61