How To 'Find Devices' On The Loop Circuit - Honeywell GENT Nano panel-based Commissioning Instructions

Fire detection and alarm system
Table of Contents

Advertisement

Commissioning instructions

How to 'Find Devices' on the Loop circuit

To check the physical location of devices on the loop circuit you will need two people in communication with each other. While one person walks around the site and marks off the devices found on a
copy of the as fitted wiring drawings, the other person operates the panel controls. The 'find device' function is used to provide a visual or audible indication at the respective device on the loop circuit.
Method 1:
Select the device and switch ON 'Find' to find the device. You will need to be at Access Level 3 or above to find devices on the loop circuit using this method.
Menu
Settings
Select
Method 2:
To 'fast find' a device on the loop circuit you will need to enable the option in the 'Fast find' form and then enter the device number to find. You can then scroll to find the next or previous device.
You will need to be at Access Level 4 to fast find devices on the loop circuit.
Menu
Engineering
Select
"
When using the Find device function at an interface it will cause its output channels to activate.
26
Loop
>
Select
Loop
>
Select
Control
Device : [
1] Settings
Label:[Device Label
2
Type
: O H Sensor sounder strobe
Devices
Assigned to Zone:[ 1]
Sensitivity States
Output Level:[-0dB ]
Save
This example shows the display of a
Dual Optical Sensor Sounder and Strobe
Select 'Yes' for Fast find otherwise select
'No' for no fast find (factory setting).
>
Select
Fast Find
Select a 'Device' from a range 1 to 127
To scroll the
range
10:15 Tue 16/02/10
Find [OFF]
'Find Device' ON / OFF option
]
Sect: [ 1]
ML:[OFF]
Save
Night: [ 0]
Day:[ 0]
Mode:[TONE]
Quit
To scroll the
To move to
next setting
range
16:15 Tue 16/02/10
Fast Find
Fast Find Enabled: [NO ]
Device Number: [
1]
Select
WARNING: Find will action relay outputs!
Enter a 'Device' from a range 1 to 127
and then scroll devices