How 'Cause and Effect' interact with 'Day and Night Modes'

This page illustrates the immediate and delayed Cause and Effect interaction with Day and Night modes.
¨
The immediate actions of a zone will always occur immediately in the event of a fire from the zone regardless of Day/Night mode status.
¨
The delayed actions of a zone will occur after the day mode delay has timed out when 'Day mode' is active. Additional verify delay will apply if it is set up and made active
during day mode delay.
Factory Default actions
(Can be changed to custom settings)
Fire Event
'Day mode'
active
Delay
Factory Default actions
(Can be changed to custom settings)
Fire Event
'Day mode'
inactive
Delay
"
By configuring the immediate actions same as delayed actions it is possible to use the Day/Night mode switching to switch sensor sensitivity states.
4188-949 issue 3_05/10_Nano Comms inst.
No action
No action
No action
Delay can be
Fire
up to
Master
Relay
10 minutes max.
Alarms
(Factory default
Sectors
is 30 seconds).
Zone 'Immediate C&E'
No action
No action
No action
Fire
Master
Relay
Alarms
Sectors
Zone 'Immediate C&E'
Evacuate
Action
Action
Action
Fire
Master
Relay
Alarms
Sectors
Zone 'Delayed C&E'
Evacuate
Action
Action
Action
Fire
Master
Relay
Alarms
Sectors
Zone 'Delayed C&E'
Nano panel based system
The final output after the delay
is the amalgamation of
ACTIVE HIGH PRIORITY ACTIONS
of both Immediate and Delayed C&E.
The final output is the
amalgamation of
ACTIVE HIGH PRIORITY ACTIONS
of both Immediate and Delayed C&E.
C&E - Cause and Effect