Measuring The Loop Cable Resistance And Capacitance; When To Use The 'Repair' Function On The Loop Circuit - Honeywell GENT Nano panel-based Commissioning Instructions
Measuring the loop cable resistance and capacitance
Power-down and disconnect both ends of the loop wiring by pulling out the associated terminal blocks at the control panel.
Resistance measurement
¨
Using a multimeter measure the resistance between the loop L1 0V (End 1) and loop L2 0V (End 2). In practice this should not be greater than 13 ohms.
Capacitance measurement
¨
Check the capacitance between the loop 0V and cable screen. The capacitance should not be greater than 1.0uF. Also the cable End-1 and End-2 should read the same value.
When to use the 'Repair' function on the loop circuit
When a loop circuit is tested for short circuit fault or if a genuine wiring short circuit fault should occur, then rectification action must be taken. First rectify the wiring fault and then
process the 'Repair' command at the control panel. You will need to be at Access level 2 or above to activate the repair function.