Figure 3-12: Wiring a Normally Closed Loop for Tamper Supervision

Figure 3-13: Wiring a Normally Open Loop for Tamper Supervision

Installing V-Plex Devices

The polling loop provides both power and data to the V-Plex devices, and is constantly monitoring the status of all zones
enabled on the loop. The maximum current draw of all devices on the polling loop cannot total more than 128mA (unless
the system uses a 4297 Polling Loop Extender Module).
Devices that can be programmed via either DIP switches or the built-in unique serial number must be set for the
serial number mode operation.
All devices on the polling loop must be wired in parallel to the [+] and [-] polling loop terminals of the control panel (24
and 25). You can wire from device to device, or have multiple branches connected directly to the control panel in a star
configuration.
Compatible Polling Loop Devices
Model Number
Type
4297
Extender Module
DT7500SN
V-Plex Dual Tech PIR
IS2500SN
V-Plex Dual Tech
4208SN
8 Zone V-Plex Interface
4208SNF
8 Zone V-Plex Class A Interface
269SN
V-Plex Holdup Switch
5193SD
Photoelectric Smoke Detector Device
5193SDT
Photoelectric Smoke Detector w/Heat Detector
4101SN
Serial Number Single-Output Relay Module
4208U
Universal 8-Zone Expander
4959SN
Aluminum Overhead Door Contact
4209U
Universal Group Zoning Module
4193SN
Serialized 2-Zone Expander
4293SN
Serialized 1-Zone Expander
4190SN
Serialized 2-Zone Expander
998MX
Serialized PIR
V-Plex VSI
V-plex Short Isolator
U L
The 4297 must be powered from the control panel's Auxiliary Power Output or from a UL Listed supplementary power
supply.
+
SENSOR
TAMPER
SWITCH
2k EOLR
+
TAMPER
SWITCH
SENSOR
2k EOLR