Accenta/Optima Engineer's Manual

Entering/Exiting Engineer Program Mode

NOTE: The factory configured engineer's access code is 9999. If however this code is changed then enter
the appropriate code.
Press
Enter Your Code
0>Walk test
To exit Engineer program mode press

Defaulting Panel to Factory Settings

CAUTION:
All configurations of the panel are reset to factory default conditions.
To default to factory settings:
1.
Power down panel.
2.
Remove wiring from SET output and PA input.
3.
Fit shorting wire between SET and left-hand PA terminal.
4.
Power up.
5.
Wait for alarm to start.
6.
Power down panel and then restore original wiring.

Defaulting User Code 1 and Engineer Code

1.
Power down panel.
2.
Remove wiring from SET output and TAMP input (next to PA).
3.
Fit shorting wire between SET and left-hand TAMP terminal.
4.
Power up.
5.
Wait for alarm to start.
6.
Power down panel and then restore original wiring.
LCD Indications
LED Indications
17