Entering/Exiting Engineer Program Mode

NOTE: The factory configured engineer's access code is 9999. If however this code is changed then enter
the appropriate code.
Press
PROG
Enter Your Code
Enter Your Code
Enter Your Code
Enter Your Code
Enter Your Code
0>Walk test
0>Walk test
0>Walk test
0>Walk test
0>Walk test
To exit Engineer program mode press

Defaulting Panel to Factory Settings

CAUTION:
All configurations of the panel are reset to factory default conditions.
To default to factory settings:
1.
Power down panel.
2.
Remove wiring from SET output and PA input.
3.
Fit shorting wire between SET and left-hand PA terminal.
4.
Power up.
5.
Wait for alarm to start.
6.
Power down panel and then restore original wiring.

Defaulting User Code 1 and Engineer Code

1.
Power down panel.
2.
Remove wiring from SET output and TAMP input (next to PA).
3.
Fit shorting wire between SET and left-hand TAMP terminal.
4.
Power up.
5.
Wait for alarm to start.
6.
Power down panel and then restore original wiring.