Page 1
NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual Specification Number: 554631 Model Number: 211...
Page 2
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual TABLE OF CONTENTS Admonishments Used in this Document ..........................iv Important Safety Instructions ..............................v Safety Admonishments Definitions ............................................v Safety and Regulatory Statements ............................................v Déclarations de Sécurité et de Réglementation ......................................v 1 Introduction ....................................1...
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual Admonishments Used in this Document will likely DANGER! Warns of a hazard the reader be exposed to that will result in death or serious injury if not avoided. (ANSI, OSHA)
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual Important Safety Instructions Safety Admonishments Definitions Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page iv. Safety and Regulatory Statements Refer to Section 4154 (provided with your customer documentation) for Safety and Regulatory Statements.
1.1 Description The Vertiv™ NetSure™ 211 Series -48 VDC battery cabinet can be mounted in a 19” or 23” relay rack or mounted to a wall. The battery cabinet contains one (1) 40 A battery disconnect circuit breaker and provides alarm leads attached to the common contacts of the breaker.
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual 1.3 Specifications Environmental Ratings • Operating Ambient Temperature Range: -40 °C to +65 °C. • Storage Ambient Temperature Range: -40 °C to +85 °C. • Humidity: This unit is capable of operating in an ambient relative humidity range of 0% to 95%, non-condensing.
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual 2.3.1 Relay Rack Method Procedure Refer to Figure 2.1 and install the 19” or 23” relay rack mounting angles to the battery cabinet. Mounting hardware is provided with the battery cabinet. Torque these connections to 46 in-lbs.
Page 10
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual Figure 2.2 Connectors and Wires Moved to the Side Install the frame ground landing point adapter P/N 556872 to the left or right side of the battery cabinet, as shown in Figure 2.3.
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual Figure 2.4 Mounting the Battery Cabinet to a Wall 0.406” mounting holes WALL 2.4 Connecting Battery Cabinet(s) to the Associated Power System Battery Leads Cables with connectors are provided on the associated power system and the battery cabinet to allow simple interconnections between a battery cabinet and the associated power system and between battery cabinets.
Page 12
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual Figure 2.5 Connecting Multiple Battery Cabinets POWER SHELF BATTERY CABINET MAIN BATTERY CABINET SUPPLEMENTAL (OPTIONAL) BATTERY CABINET SUPPLEMENTAL (OPTIONAL) Battery Disconnect Circuit Breaker Alarm Leads Procedure Furnished with the battery cabinet are battery disconnect circuit breaker alarm lead assemblies. Refer to the power system installation manual to use these alarm leads to connect the battery cabinet battery disconnect circuit breaker alarm into the power system alarm circuits.
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual 2.5 Installing GNB M12V40F Batteries Procedure Unscrew the front cover panel from the battery cabinet. Place the spacers in between the batteries. Refer to Figure 2.6. NOTE! Place the two supplied spacers (P/N 545511) side by side, and follow with the other spacer (P/N 545538) on top.
Page 14
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual Figure 2.7 Connecting GNB M12V40F Batteries - Wire Supplied cables + Wire Attach the cabinet wires to + and - terminals. Refer to Figure 2.8. Figure 2.8 Connecting GNB M12V40F Batteries to (+) and (-) Terminals...
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual 2.6 Securing the Batteries Using the Strap Procedure Pull strap such that enough length is provided to secure the batteries. Hold the buckle such that the strap can slip into inner slot of the buckle. See Figure 2.9 for reference.
Vertiv™ NetSure™ 211 Series -48 VDC Battery Cabinet Installation and User Manual To release buckle, pull outward on free strap end. Figure 2.11 Securing the Batteries in the Cabinet 2.7 Typical Internal Wiring Layout Figure 2.12 Typical Internal Wiring Layout...
Need help?
Do you have a question about the NetSure 211 Series and is the answer not in the manual?
Questions and answers