Summary of Contents for Vertiv NetSure 2100 Series
Page 1
NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000), Revision A Specification Number: 582138000 Model Number: 2100...
Page 2
Vertiv Group Corporation is strictly prohibited. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners.
Replacing a Rectifier ............................... 16 Replacing the Mini Control Unit ........................16 Replacing a GMT Distribution Fuse ......................17 Replacing a Bullet Nose Circuit Breaker....................19 Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
Page 4
Replacing the External IB4 Assembly (if furnished) ............... 20 Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
SAFETY! Informs the reader of general safety information, reminders, precautions, or policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA) Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
DANGER! Follow local lockout/tagout procedures to ensure DC branch circuit protection devices remain de-energized during installation at loads, as required. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
• Do not open or mutilate batteries. • ALWAYS FOLLOW THE BATTERY MANUFACTURER’S RECOMMENDATIONS AND SAFETY INSTRUCTIONS. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
NOTE! When performing any step in procedures that requires removal of existing hardware, retain all hardware for use in subsequent steps, unless otherwise directed. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
If necessary to repair equipment containing static sensitive components, wear an appropriately grounded wrist strap, work on a conductive surface, use a grounded soldering iron, and use grounded test equipment. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
Page 10
This Page Intentionally Blank. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
For factory settings of all configurable controller parameters, refer to the Configuration Drawing (C-drawing) supplied with your power system. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
Various distribution unit options are available. See SAG582138000 for descriptions. The distribution unit can be equipped with an optional Low Voltage Battery Disconnect (LVBD) contactor. The various distribution units provide DC distribution through circuit breakers and/or fuses. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
Local Controls and Indicators Controller and Rectifier Refer to the controller and rectifier instructions for descriptions of the local controls and indicators located on these units. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
To increase system current capacity, a rectifier module can easily be added if an empty rectifier module mounting position is available. Refer to rectifier instructions UM1R481000e3 for a rectifier installation procedure. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
If that happens, the current limit point will automatically decrease to the maximum (121% of the remaining rectifiers). It is recommended that the current limit point be checked whenever a rectifier is added to or removed from the power system. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
Rectifiers” in the separate power system installation manual (IM582138000). Replacing the Mini Control Unit Refer to the mini control unit instructions (UM1M831ANA) for a controller replacement procedure. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
Breaker distribution unit. Load Disconnect Circuit Breakers OFF Position Towards Center Turn circuit breaker off before installing. Components removed in illustration for clarity only. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
Page 20
Enable the external alarms, or notify appropriate personnel that this procedure is finished. Ensure that there are no local or remote alarms active on the system. Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...
Page 21
(not used) Port (RJ-45) LAN Connection USB-B Port Top Cover (Customer connected to power shelf via Removed supplied cable.) USB-B Port (Customer connected to power shelf.) Vertiv | NetSure™ 2100 Series -48 VDC Power System User Manual (UM582138000) | Rev. A...