E8: Standard communication parameters

Code
Name
Communication error
E8.01
detection time
Communication error
E8.02
protection mode
Communication process
E8.03
data loss behavior
E8.10 Modbus baud rate
E8.11 Modbus data format
E8.12 Modbus local address
Modbus level / edge sen-
E8.13
sitivity selection
Setting range of E8.11:
0: N, 8, 1 (1 start bit, 8 data bits, 1 stop bit, no parity)
1: E, 8, 1 (1 start bit, 8 data bits, 1 stop bit, even parity)
2: O, 8, 1 (1 start bit, 8 data bits, 1 stop bit, odd parity)
3: N, 8, 2 (1 start bit, 8 data bits, 2 stop bits, no parity)
246/253
Setting range
0.0...60.0 s
(0.0: Inactive)
0: Freewheeling stop
1: Keep running
2: Emergency stop
0: Decelerating stop
1: Freewheeling stop
2: Keep running
0: 1,200 bps; 1: 2,400 bps
2: 4,800 bps; 3: 9,600 bps
4: 19,200 bps; 5: 38,400 bps
0...3
1...247
0: Level sensitive
1: Edge sensitive
VFC 3210
Default
Min.
0.0
0.1
1
0
3
0
1
1
1
DOK-RCON04-VFC3210****-IT01-EN-P
Attri.
Stop
Stop
Stop
Stop
Stop
Stop
Stop