Quick Start; Checklist Before Quick Start; Step 1: Check Application Conditions; Step 2: Check Mounting Conditions - Bosch Rexroth VFC 3210 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for Rexroth VFC 3210:
Table of Contents

Advertisement

VFC 3210

11 Quick Start

11.1 Checklist before Quick Start

11.1.1 Step 1: Check application conditions

Rated ambient temperature
Derating / ambient temperature
Rated storage temperature
Rated altitude
Derating / altitude
Mounting mode
Tab. 11-1: Application conditions checklist
See also in
chapter 6.1.8 "Conditions" on page

11.1.2 Step 2: Check mounting conditions

Converter mounting direction
Minimum top space
Minimum bottom space
One converter is arranged above another
Mounting screws
Tab. 11-2: Mounting conditions checklist
See also in
chapter 7.1 "Installation Conditions" on page

11.1.3 Step 3: Check the wiring

Mains connection
Motor connection
Grounding
Shielding
Power cables
Control terminals connection
Control cables
EMC
Switches
Load
Tab. 11-3: Wiring checklist
DOK-RCON04-VFC3210****-IT01-EN-P
-10...40 ℃
1.5 % / 1 °C (40...50 °C)
-20...60 ℃
≤ 1,000 m
1 % / 100 m (1,000...2,000 m)
Wall mounting
21.
Vertical
d
= 150 mm
top
d
= 150 mm
bot
Air guide available is required in between
2 x M4 or 4 x M4, no loose screws
Connect L1, L2, (L3) of converter to mains accordingly
Connect U, V, W of converter to motor accordingly
Must be securely connected
Must be securely connected
Must observe
chapter 8.1 "Wiring Diagram" on page 31
Must be securely connected
Must observe
chapter 8.2.2 "Control Cables" on page 35
Must observe
chapter 9 "Electromagnetic Compatibility
(EMC)" on page 44
Must be switched off
Must be disconnected
Bosch Rexroth AG
Quick Start
26.
69/253

Advertisement

Table of Contents
loading

Table of Contents