12.10.2 Reaction to External Error Signals

The frequency converter stops once an external error signal is active and the
error code 'E-St' will be displayed on the operating panel if one X1...X4 input is
defined as either 'Error signal N.O. contact input' or 'Error signal N.C. contact in-
put'.
Code
Name
E1.00
X1 input
E1.01
X2 input
E1.02
X3 input
E1.03
X4 input
E0.56
Emergency stop action
Emergency stop decelera-
E0.57
tion time
32: Error signal N.O. contact input
– If the defined switch is closed, the external error signal is active.
– If the defined switch is open, the external error signal is inactive.
33: Error signal N.C. contact input
– If the defined switch is open, the external error signal is active.
– If the defined switch is closed, the external error signal is inactive.
Frequency converter stops when external error signal is active. Stop mode is de-
fined by parameter E0.56:
E0.56 = 0: Freewheeling stop
E0.56 = 1: Decelerating stop. The deceleration time is defined by parameter
E0.57.
Example:
Set [E1.00] = '32: Error signal N.O. contact input' or
Set [E1.01] = '33: Error signal N.C. contact input'
Fig. 12-45: Error signal
DOK-RCON04-VFC3210****-IT01-EN-P
Setting range
32: Error signal N.O. contact input
33: Error signal N.C. contact input
0: Freewheeling stop
1: Decelerating stop
0.1...6,000.0
Bosch Rexroth AG
Functions and Parameters
Default
Min.
35
36
0
0
0
5.0
0.1
Attri.
Stop
Stop
Stop
Stop
Stop
Run