Functions and Parameters
Used for the 3-wire control mode, see
(Forward / stop, reverse / stop)" on page
26: Simple PLC stop; 27: Simple PLC pause
Used for the simple PLC to stop and pause a PLC cycle, see
"Stop and Pause Simple PLC Control" on page
30: Second frequency setting source activation
Used for switching to the second frequency setting source, see
quency setting source switching" on page
31: Second run command source activation
Used for switching to the second run command source, see
between first and second run command source" on page
32: Error signal N.O. contact input
33: Error signal N.C. contact input
Used for receive error signal from external sources, see
tion to External Error Signals" on page
34: Error reset input
Used for error reset operation, see
184.
35: Forward running (FWD); 36: Reverse running (REV)
Used for Run / Stop command control, see
tion Command Source" on page
37: Forward jog; 38: Reverse jog
See
chapter 12.6.2 "Jog Function" on page
39: Counter input; 40: Counter reset
See
chapter 12.7.1 "Counter Function" on page
41: PID deactivation
See
chapter 12.9 "PID Control" on page
46: User parameter set selection
48: Motor overheating error N.O. contact input
49: Motor overheating error N.C. contact input
50: Motor overheating warning N.O. contact input
51: Motor overheating warning N.C. contact input
80/253
chapter 12.6.3 "2-wire / 3-wire Control
123.
136.
91.
155.
chapter 13.5 "Error Handling" on page
chapter 12.5 "Run- / Stop- / Direc-
107.
121.
127.
139.