12.8.2 Set the Simple PLC Mode

Code
Name
E3.00
Simple PLC running mode
E3.01
Simple PLC time multiplier 1...60
E3.02
Simple PLC cycle number
[E3.00] = 0: Inactive
[E3.00] = 1: Stop after selected cycle
In this mode, the frequency converter decelerates to 0.00 Hz after the last
stage of simple PLC, and then stops according to the configured stopping
mode.
[E3.00] = 2: Continuously cycling
In this mode, the frequency converter decelerates to 0.00 Hz after the last
stage of simple PLC, and then starts a new cycle automatically.
[E3.00] = 3: Run last stage after selected cycle
In this mode, the frequency converter keeps running at the setting frequency
of the last stage of simple PLC.
The actual duration for each stage is defined by following equation (Take stage 0
as an example):
T
= [E3.61] x [E3.01]
Run
Based on the equation above, the maximum duration of one cycle is:
8 x 6,000.0 s x 60 = 800 hours.
DOK-RCON04-VFC3210****-IT01-EN-P
Setting range
0...3
1...1,000
Bosch Rexroth AG
Functions and Parameters
Default
Min.
0
1
1
1
1
Attri.
Stop
Stop
Stop
133/253