Fig. 12-55: User-defined V/f curve when [C2.05] ≥ [C1.08]

Slip compensation factor configuration

This function is used to compensate [C1.12] 'Motor rated slip compensation' ac-
cording to the actual applications in V/f control.
Code
Name
C2.07
Slip compensation factor
0 %: No slip compensation
The slip compensation function is deactivated.
1...100 %: Full slip compensation
Example: [C1.12] = 2.50 Hz, [C2.07] = 100 %
The actual slip compensation is 2.50 Hz x 100 % = 2.50 Hz.
101...200 %: Over slip compensation
Example: [C1.12] = 2.50 Hz, [C2.07] = 200 %
The actual slip compensation is 2.50 Hz x 200 % = 5.00 Hz.
DOK-RCON04-VFC3210****-IT01-EN-P
Functions and Parameters
Setting range
0...200 %
Bosch Rexroth AG
Default
Min.
Attri.
0
1
Run
169/253