12.7 Special Functions

12.7.1 Counter Function

The internal counter counts the input pulses received from 'digital input' and
compares it with the setting value of 'Counter middle value' or 'Counter target
value'.
The 'Counter middle value arrival' or 'Counter target value arrival' output signal
will be indicated via DO1 or Relay 1 output when the counter value equals to
that of setting value.
The counter is cleared and the DO1 or Relay 1 output signal is reset by a valid
edge signal of another digital input defined as 'Counter reset'.
Code
Name
E1.00 X1 input
E1.01 X2 input
E1.02 X3 input
E1.03 X4 input
E2.80 Counter middle value
E2.81 Counter target value
E2.15 Relay 1 output selection
Example:
X1 input is defined as '39: Counter input'.
X2 input is defined as '40: Counter reset'.
The wiring is shown as the figure below:
Fig. 12-30: Digital input configuration
Connected K1 to X1, and set [E1.00] = '39: Counter input'.
Connected K2 to X2, and set [E1.01] = '40: Counter reset'.
DOK-RCON04-VFC3210****-IT01-EN-P
Setting range
39: Counter input
40: Counter reset
0...[E2.81]
[E2.80]...9,999
16: Counter target value arrival
17: Counter middle value arrival
Bosch Rexroth AG
Functions and Parameters
Default
Min.
35
36
0
0
0
1
0
1
1
Attri.
Stop
Stop
Stop
Stop
Run
Run
Stop
127/253