14.3.6 Special Notes

1. The external computer can not write to function codes b0.11 'Parameter
copy', U1.00 'running monitoring display' and U1.10 'Stop monitoring dis-
play'.
2. b0.20 'User password' and b0.10 'Parameter initialization' do not support
multiple write including single write in multiple write; Motor nameplate pa-
rameters and motor physical data should not be modified simultaneously;
Multi-function digital input terminals (E1.00...E0.04) writing operation do
not permit repeated non-zero value.
3. If the communication protocol is changed, baud rate, data frame and local
address will be restored to factory default.
4. The read response of user password and manufacture password is '0000'
in case of external computer reading.
5. The external computer can set, modify or cancel user password, the specif-
ic operation is same to the situation when 'Running command source' is
from the operating panel.
6. The access to control registers and state registers is not limited by user
password.