Stop Behavior Setting; Stop Mode Setting - Bosch Rexroth VFC 3210 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for Rexroth VFC 3210:
Table of Contents

Advertisement

Bosch Rexroth AG
Functions and Parameters

12.5.5 Stop Behavior Setting

Stop mode setting

Code
Name
E0.50 Stop mode
E1.00 X1 input
E1.01 X2 input
E1.02 X3 input
E1.03 X4 input
[E0.50] = 0: Deceleration stop
The motor decelerates to stop according to the defined deceleration time.
If 'Output frequency' is lower than [E0.52] 'Stop DC-braking initial frequency'
and 'Stop DC-braking time' [E0.53] ≠ 0, and then DC-braking is activated. The
'Stop DC-braking current' is decided by [E0.54].
[E0.50] = 1: Freewheeling stop 1
Once the stopping command is activated, the converter stops output and the
motor mechanically freewheels to stop.
'Freewheeling stop' can also be activated by digital inputs. When the digital
input signal is active, the frequency converter freewheels to stop. If the digital
input signal is inactive and a run command is active, the frequency converter
resumes the previous running status.
[E0.50] = 2: Freewheeling stop 2
– When stopping command is active, the motor freewheels to stop as [E0.50]
= 1.
– When direction command is changed during running, the motor deceler-
ates to stop according to the defined deceleration time as [E0.50] = 0.
If an error occurs due to too fast deceleration, increase the decelera-
tion time or calculate if additional resistor braking is necessary.
116/253
Setting range
0...2
15: Freewheeling stop activation
VFC 3210
Default
Min.
0
35
36
0
0
DOK-RCON04-VFC3210****-IT01-EN-P
Attri.
Stop
Stop
Stop
Stop
Stop

Advertisement

Table of Contents
loading

Table of Contents