12.5.4 Start Behavior Setting

Start mode selection

Code
Name
E0.35 Start mode

Start directly

This mode is used in applications with high static friction torque and low load
inertia. The frequency converter runs at [E0.36] 'Start frequency', for [E0.37]
'Start frequency holding time', and then accelerates to setting frequency with
defined acceleration time.
Code
Name
E0.36 Start frequency
E0.37 Start frequency holding time 0.0...20.0 s
Fig. 12-19: Start directly
Set parameter E0.37 'Start frequency holding time' to a non-zero val-
ue when the motor needs to be started with certain start frequency.
DOK-RCON04-VFC3210****-IT01-EN-P
Setting range
0: Start directly
1: DC-braking before start
2: Start with speed capture
3: Automatic start / stop accord-
ing to setting frequency
Setting range
0.00...50.00 Hz
Bosch Rexroth AG
Functions and Parameters
Default
Min.
0
Default
Min.
0.05
0.01
0.0
0.1
Attri.
Stop
Attri.
Stop
Stop
111/253