Bosch Rexroth AG
Functions and Parameters
12.9.9 Sleep / Wake Function
This function is used to achieve the maximum extent of energy-saving according
to type of loads in actual applications.
Code
E5.15 Sleep level
E5.16 Sleep delay
E5.17 Sleep boost time
E5.18 Sleep boost amplitude
E5.19 Wake up level
E5.20 Wake up delay
The frequency converter may go into the sleep mode when all the conditions be-
low are met:
[PID feedback] > [E5.19] 'Wake up level'
●
[PID output] < [E5.15] 'Sleep level'
●
[Duration] t ≥ [E5.16] 'Sleep delay'
●
146/253
Name
0.00...[E0.09] Hz
0.0...3,600.0 s
0.0...3,600.0 s
0.0...100.0 %
0.0...100.0 %
0.2...60.0 s
Setting range
Default
DOK-RCON04-VFC3210****-IT01-EN-P
VFC 3210
Min.
Attri.
0.00
0.01
Run
60.0
0.1
Run
0.0
0.1
Run
0.0
0.1
Run
0.0
0.1
Run
0.5
0.1
Run