5 Configuration of the system

5.2 Network Variable Description

5.2.1 - FC VSD Profile - input
Start/Stop
Variable
name:
nviStartStop
5
This variable sends a Start or Stop command to the frequency converter and a reference (0 - 100 %)
NB!
The reference value of nviStartStop will only be valid
if both nviRefPcnt and nviRefHz are = 0
Control Word
Variable
name:
nviControlword
The input network variable nviControlWord is a 16-bit word providing additional operational control of the frequency converter.
For more information about the Control word, please refer to the
NB!
Please note in the representation of the Control Word in the LonMaker Browser, the LSB is to the far left.
Reset fault
Variable
name:
nviResetFault
This variable sends a reset command to the frequency converter via bit 7 in the Control Word (0x04BC), see the
22
SNVT
State:
type:
SNVT_switch
0 (False)
1 (True)
1 (True)
1 (True)
0xFF (default)
SNVT
type:
SNVT_state
Danfoss FC Control Profile
SNVT
State:
type:
SNVT_switch
0 (False)
1 (True)
0xFF (default)
MG.11.E2.02 - VLT
Value:
Any
0
1-200
201-255
Any
Boolean 1 bit x 16
section.
Value:
Any
Any
Any
AUTO (invalid, no action)
Danfoss FC Control Profile
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Command:
Stop (0x043C)
Running 0% (0x047C)
Running 0.5 to 100.0%
Running100%
AUTO (invalid, no action)