5 Configuration of the system

5.8 Network Timer Functions

5.8.1 Control Word Time-out Function
par.8-03
Control Timeout Time
controller node.
If a valid control word has not been received within the time specified in par. 8-03, the action specified in par. 8-04 will be performed. The default action
is OFF (no action).
The range of par. 8-03 is: 0.1 to 18,000 seconds (or 5 hours).
An update of the control word is triggered by the following SNVT's:
nviStartStop
5
nviResetFault
nviControlword
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
nviFeedback 1,2,3
nviSetPoint 1,2,3
5.8.2 Min. Send Time (Inhibit Timer)
Variable
name:
nciMinSendT
Variable used for limiting bus traffic by setting a minimum sending timer (inhibit timer).
Applies for all output variables.
Format: Days Hours:Minutes:Seconds:Milliseconds.
40
and par.8-04
Control Timeout Function
SNVT
type:
SNVT_elapsed_tm
MG.11.E2.02 - VLT
provide a means for the frequency converter to control communication to a
Default value:
Min value:
00:0:0:500
0 0:0:0:100
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Max value:
0 0:01:05:535