Node Object - Danfoss VLT FC 100 LonWorks Manual

Hide thumbs Also See for VLT FC 100 LonWorks:
Table of Contents

Advertisement

VLT® FC 100 LonWorks

5.7 Node Object

5.7.1 Node Object
5.7.2 Object Request
Variable name:
SNVT type:
nviRequest
SNVT_obj_request
5.7.3 Object Response
Variable name:
SNVT type:
nvoStatus
SNVT_object_status
5.7.4 Max. Send Time (Heartbeat)
Variable
SNVT
name:
type:
nciMaxStsSendT
SNVT_elapsed_tm
This variable configures a timer to send the nvoStatus object but only if bound to an input variable.
Maximum is '0 17:59:59:999' (0 days, 17 hours, 59 minutes, 59 seconds and 999 milliseconds).
Setting the timer to '0 0:0:0:0' disables it.
Network timer functions monitor node presence and control behaviour in the event of network problems occurring.
Supported functions:
RQ_Normal
RQ_Update_Status
RQ_Report_Mask
RQ_Disabled
RQ_Enable
This output network variable reports the status for any functional block on a device. It is also used to report
the status of the entire device and all functional blocks on the device.
Default value:
00:0:0:0
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
5 Configuration of the system
These variables are used for controlling all functional blocks via the com-
missioning tool.
Description:
Returns the specified functional block to normal operation.
Requests the status of the specified functional block.
Requests a status mask reporting the status bits that are supported
by the specified functional block.
Requests the specified functional block to change to the disabled
state. In the disabled state, output network variables belonging to
the functional block are not propagated within the network.
Requests the specified functional block to change to the enabled
state. In the enabled state, output network variables belonging to
the functional block are propagated within the network as defined
by the functional block.
Description:
Min value:
00:0:0:0
5
Max value:
017:59:59:999
39