Parameter Group - Danfoss VLT FC 100 LonWorks Manual

Hide thumbs Also See for VLT FC 100 LonWorks:
Table of Contents

Advertisement

8 Parameters

8.3 Parameter Group 11

11-00 Neuron ID
Range:
0 N/A*
[0 - 0]
11-10 Drive Profile
Option:
[0] *
VSD profile
11-15 LON Warning Word
Range:
0 N/A*
[0 - FFFF ]
Bit
0
1
2
8
3
4
5
6
7
8
9
10
11
12
13
14
15
11-17 XIF Revision
Range:
0 N/A*
[0 - 0]
11-18 LonWorks Revision
Range:
0 N/A*
[0 - 0]
11-21 Store Data Values
Option:
[0] *
Off
[2]
Store all setups
54
Function:
View the Neuron chip's unique Neuron ID number.
View the Neuron chip's unique Neuron ID number.
Function:
This parameter allows selecting between LONMARK Functional Profiles.
The Danfoss Profile and the Node Object are common for all profiles.
Function:
This parameter contains the LON specific warnings.
Status
Internal fault
Internal fault
Internal fault
Internal fault
Internal fault
Reserved
Reserved
Reserved
Reserved
Invalid type change for changeable types
Initialization error
Internal communication error
Software revision mismatch
Bus not active
Option not present
LON input (nvi/nci) exceeds limits
Function:
This parameter contains the version of the external interface file on the Neuron C chip on the LON
option.
Function:
This parameter contains the software version of the application program on the Neuron C chip on
the LON option.
Function:
This parameter is used to activate storing of data in non-volatile memory.
Store function is inactive.
Stores all parameter values in the E
been stored.
MG.11.E2.02 - VLT
2
PROM. The value returns to
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Off
when all parameter values have

Advertisement

Table of Contents
loading

Table of Contents