5 Configuration of the system
5.1.3 FC VSD Profile
The FC VSD Profile describes all Danfoss VLT specific network variables.
5
Input variables
Variable Function
Start/Stop
Control word
Reset fault
Reference [%]
Reference [Hz]
CL Setpoint 1
CL Setpoint 2
CL Setpoint 3
Bus feedback 1
Bus feedback 2
Bus feedback 3
Digital/relay outputs
Analog output (42)
Analog output (X30/8)
Analog output (X42/7)
Analog output (X42/9)
Analog output (X42/11)
Setting of RTC
ECB option Mode
ECB By-pass activation
Parameter access command nviParamRequest
20
Variable Name
SNVT type
nviStartStop
SNVT_switch
nviControlword
SNVT_state
nviResetFaut
SNVT_switch
nviRefPcnt
SNVT_lev_percent
nviRefHz
SNVT_freq_hz
nviSetpoint1
SNVT_lev_percent
nviSetpoint2
SNVT_lev_percent
nviSetpoint3
SNVT_lev_percent
nviFeedback1
SNVT_lev_percent
nviFeedback2
SNVT_lev_percent
nviFeedback3
SNVT_lev_percent
nviDigiOutput
SNVT_state_64
nviAnOut1
SNVT_lev_percent
nvi101AnOut1
SNVT_lev_percent
nvi109AnOut1
SNVT_lev_percent
nvi109AnOut2
SNVT_lev_percent
nvi109AnOut3
SNVT_lev_percent
nviTimeStamp
SNVT_time_stamp
nviECBMode
SNVT_state
nviECBActivation
SNVT_switch
UNVT_param_request
MG.11.E2.02 - VLT
Profile
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
FC VSD
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
FC 100 par.
CTW/reference
CTW
CTW
Reference
Reference
20-21
20-22
20-23
8-94
8-95
8-96
5-90
6-53
6-63
26-43
26-53
26-63
0-70
31-00
31-19
-