Danfoss VLT FC 100 LonWorks Manual page 13

Hide thumbs Also See for VLT FC 100 LonWorks:
Table of Contents

Advertisement

VLT® FC 100 LonWorks
4.1.4 Connecting the Bus Line
Connect bus wire NET A to terminal 79 and NET B to 80 of the terminal connector.
Terminal
NB!
*Note: For free topology wiring the option is insensitive to the polarity of the bus-terminals.
NB!
**Note: Term. 61 (Drain) offers a RC-junction to ground and should not be used for grounding of shielded cable. Ground the shielded
cable at the de-coupling plate by removing cable insulation at contact point.
4.1.5 Maximum Cable Lengths
Network topology
Free topology without repeater
Free topology with one repeater
Free topology maximum device-to-device
Bus topology single terminated
Bus topology double terminated without repeater
Bus topology double terminated with one repeater
Bus topology maximum stub length
Use of the same cable type throughout the entire network is recommended in order to avoid impedance mismatch.
4.1.6 System Specifications
Up to 64 FT-X1/FTT-10 transceivers, are allowed per network segment.
NB!
Note: The Free Topology LonWorks runs at 78 Kbps only.
79
80
61
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
4 How to install
Connection
NET A*
NET B*
Drain**
Maximum cable length
500 m
1000 m
500 m
500 m
2700 m
5400 m
3 m
4
13