Danfoss VLT FC 100 LonWorks Manual page 50

Hide thumbs Also See for VLT FC 100 LonWorks:
Table of Contents

Advertisement

8 Parameters
[2]
USB Port
[3] *
Option A
[4]
Option B
[5]
Option C0
[6]
Option C1
NB!
This parameter cannot be adjusted while the motor is running.
8-03 Control Timeout Time
Range:
60.0 s*
[1.0 - 18000.0 s]
8
8-04 Control Timeout Function
Option:
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
[20]
N2 Override Release
In LonWorks, the time-out function is also activated when the following SNVT's fail to be updated within the time period specified in par.8-03
Timeout Time
:
nviStartStop
nviReset Fault
nviControlWord
50
Function:
Enter the maximum time expected to pass between the reception of two consecutive telegrams. If
this time is exceeded, it indicates that the serial communication has stopped. The function selected
Control Timeout Function Control Time-out Function
in par.8-04
In LonWorks the following variables will trigger the Control Word Time parameter:
nviStartStop
nviReset Fault
nviControlWord
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
Function:
Select the time-out function. The time-out function is activated when the control word fails to be
updated within the time period specified in par.8-03
after setting the N2 protocol.
nviDrvSpeedStpt
nviRefPcnt
nviRefHz
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
will then be carried out.
Control Timeout Time
. Choice [20] only appears