5 Configuration of the system
These variables contain the value allocated to the analog output terminal X42/7-11 of the
commissioning tool.
NB!
This variable is available only if the Analog I/O option (MCB 109) has been installed.
Setting of RTC
Variable
name:
nviTimeStamp
5
Use this input to set the built-in Real Time Clock.
ECB Option Mode
Variable
name:
nviECBMode
Controls the operation mode of the ECB option. The binary value of this variable is mapped directly into par. 31-00
[0] Drive
[1] Bypass
ECB Remote By-pass Activation
Variable
name:
nviECBActivation
Controls the remote activation of the ECB option.
The binary value of this variable is mapped directly into par. 31-90.
[0] Disabled
[1] Enabled
NB!
This input variable applies only if the ECB option is installed in the frequency converter.
Parameter Access Command
Variable
name:
nviParamRequest
These input variables are used for for frequency converter parameter access.
For more information on parameter access, please refer to
26
SNVT
type:
SNVT_time_stamp
Year
2000 -3000
SNVT
type:
SNVT_state
SNVT
type:
SNVT_state
SNVT
type:
SNVT_param_request
How to Access FC 100 Parameters
MG.11.E2.02 - VLT
Analog I/O option
. The variable type is changeable with the
Field:
Month
Day
Hour
0 - 12
0 - 31
0 - 23
State:
Boolean 1 bit x 16
State:
Boolean 1 bit x 16
Value:
section.
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Minute
Second
0 - 59
0 - 59
Bypass Mode
.