Danfoss VLT FC 100 LonWorks Manual page 28

Hide thumbs Also See for VLT FC 100 LonWorks:
Table of Contents

Advertisement

5 Configuration of the system
DC Link Voltage [V]
Variable
name:
nvoDCVoltage
This variable contains the measured Dc-link voltage. The value is filtered and therefore may be delayed with up to 1.3 seconds before a voltage change
is reflected in the output variable.
Motor Thermal [%]
Variable
5
name:
nvoTempMrt
This variable contains the calculated / estimated thermal load on the motor.
The cut-out limit is at 100%.
Inverter Thermal [%]
Variable
name:
nvoTempInvrtr
This variable contains the percentage thermal load of the inverters.
The cut-out limit is at 100%.
Closed Loop Feedback
Variable
name:
nvoFeedback
This variable contains the summerized amount of network feedback in closed loop mode.
Fanbelt broken
Variable
name:
nvoBrokenbelt
This variable indicates whether the fanbelt is intact or broken (indicated by bit 8 in Warning Word 2).
28
SNVT
type:
SNVT_volt
SNVT
type:
SNVT_lev_cont
SNVT
type:
SNVT_lev_cont
SNVT
type:
SNVT_count_inc_f
SNVT
type:
SNVT_switch
0 (False)
1 (True)
MG.11.E2.02 - VLT
Value:
Min.
Max.
0 V
10,000 V
Value:
Min.
Max.
0 %
100 %
Value:
Min.
Max.
0 %
100 %
Value:
Min.
Max.
0 %
100 %
State:
Value:
Any
Any
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks
Resolution:
0.1 V
Resolution:
0.5 %
Resolution:
0.5 %
Resolution:
0.5 %
Command:
Fanbelt not broken
Fanbelt broken