7 How to access FC 100 parameters
In the [Field List:] under the section [par_number], enter the parameter number (in this example 3-41). If an indexed (array) parameter is accessed, the
[subindex] field must be filled-in.
7
The response may look like this:
Value [0] (1st byte) = 232
Value [1] (2nd byte) = 3
-meaning that the readout value of parameter 3-41 is: 232+(3x256) = 1000
Conversion index of par. 3-41 is: -2(0.01)
Ramp 1 Ramp-up Time = 1000x0.01 = 10 seconds
48
MG.11.E2.02 - VLT
®
is a registered Danfoss trademark
VLT® FC 100 LonWorks