2. Commissioning
Festo P.BE−CPX−FB14−E N en 0810b
Do the following to use virtual modules in a configuration:
1. Set the CPX−FB14 into the pre−operational mode.
2. Define a possible configuration of CPX terminal with the
object 4800
(prerequisite: 4800,0 = 0 and 4000 = 0):
4800,1: module 0
4800,2: module 1
etc.
3. Write the number of the configured modules to the object
4800,0. As a result, the configuration defined by the
objects 4800,1
comparison).
In case of an incorrect nominal/actual comparison:
The object 4800,0 is set to 0, an error code is entered
in object 4801 and CPX error 29 is messaged with the
emergency message.
In case of an incorrect nominal/actual comparison:
The function assignment masks are generated
(objects 4001 and 4200) and digital outputs are reset
(object 6200).
4. Activate the masks by setting the 4000 to 1.
5. Adjust the PDO mapping (objects 160x and 1A0x) if you
defined virtual modules.
4800,x are tested (nominal/actual
2−65