Three-Phase 200 V Class Drive Models 2A0040 To 2A0211 - YASKAWA A1000 Series Quick Start Manual

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

A.2 Power Ratings
u

Three-Phase 200 V Class Drive Models 2A0040 to 2A0211

Item
Drive Model
Maximum Applicable Motor Capacity
<1>
(HP)
Input Current (A)
Rated Voltage
Rated Frequency
Input
Allowable Voltage Fluctuation
Allowable Frequency Fluctuation
Input Power (kVA)
Rated Output Capacity
<4>
(kVA)
Rated Output Current (A)
Output
Overload Tolerance
Carrier Frequency
Maximum Output Voltage (V)
Maximum Output Frequency (Hz)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> DC input is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 220 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<7> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
236
Table A.3 Power Ratings Continued (Three-Phase 200 V Class)
2A0040 2A0056
ND Rating
HD Rating
ND Rating
<2>
HD Rating
ND Rating
HD Rating
<5>
15.2
ND Rating
12.6
HD Rating
<6>
<5>
ND Rating
HD Rating
<6>
2A0069 2A0081
15
20
25
10
15
20
52
68
80
37
52
68
Three-phase 200 to 240 Vac 50/60 Hz/270 to 340 Vdc
24
31
37
17
24
31
21
26
17.9
23
<6>
<6>
40
56
69
33
47
60
<6>
<6>
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
User adjustable between 1 and 15 kHz
Three-phase 200 to 240 Vac (proportional to input voltage)
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Specification
2A0110 2A0138 2A0169 2A0211
30
40
50
25
30
40
92
111
136
80
82
111
-15 to 10%
±5%
42
51
62
37
37
51
31
42
53
29
32
44
<6>
<6>
<6>
81
110
138
75
85
115
<6>
<6>
<6>
400 Hz (user-set)
60
75
50
60
164
200
136
164
<3>
75
91
62
75
64
80
55
69
<7>
<7>
169
211
145
180
<7>
<7>
User adjustable
between 1 and
10 kHz

Hide quick links:

Advertisement

Table of Contents
loading