YASKAWA A1000 Series Quick Start Manual page 314

High performance vector control drive
Hide thumbs Also See for A1000 Series:
Table of Contents

Advertisement

B.10 o: Operator-Related Settings
No.
(Addr.
Name
Hex)
DC Bus Pre-Charge
o4-07
Relay Maintenance
(0523)
Setting
o4-09
IGBT Maintenance
(0525)
Setting
o4-11
U2, U3 Initialization
(0510)
o4-12
kWh Monitor
(0512)
Initialization
Number of Run
o4-13
Commands Counter
(0528)
Initialization
314
LCD Display
Sets the point at which the cumulative timing for the soft charge
bypass relay maintenance starts.
ChrgCircMaintSet
View monitor U4-06 to determine when the bypass relay may
require replacement.
Sets the point at which the cumulative timing for the IGBTs
maintenance starts.
IGBT Maint Set
View monitor U4-07 to determine when the IGBTs may require
replacement.
0: U2-oo and U3-oo monitor data is not reset when the drive
Fault Data Init
is initialized using A1-03.
0: Disabled
1: U2-oo and U3-oo monitor data is reset when the drive is
1: Enabled
initialized using A1-03. Parameter is automatically reset to 0.
0: U4-10 and U4-11 monitor data is not reset when the drive is
kWh Monitor Init
initialized using A1-03.
0: No Reset
1: U4-10 and U4-11 monitor data is reset when the drive is
1: Reset
initialized using A1-03. Parameter is automatically reset to 0.
0: U4-02 monitor data is not reset when the drive is initialized
Run Counter Init
using A1-03.
0: No Reset
1: U4-02 monitor data is reset when the drive is initialized using
1: Reset
A1-03. Parameter is automatically reset to 0.
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
Description
Values
Page
Default: 0%
Min.: 0
Max.: 150
Default: 0%
Min.: 0
Max.: 150
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1
Default: 0
Range: 0, 1