6.
Adjusting the system
6.1
Determining the operating times of the system
Two factors are critical in determining the run-times of the system:
1) The operating times of the kitchen for the run-time of the sieve screw.
2) The quantity of grease and oil arising in a day for the run-time of the skimmer
unit.
6.2
Setting the run-time (sieve screw)
In order to avoid the inlet being blocked and regular use of the emergency
overflow, the run-times of the sieve screw should be set to the operating times of
the kitchen. If wastewater is produced in the kitchen, the sieve screw should at
least be operational in intervals.
L The smallest cycle period for the time switch is 15 minutes. This can be set
as an operating period and/or an idle period. The system can be switched to
manual mode via the button on the control unit.
1 Ensure that the main switch has been turned to the OFF position.
▶ Loosen the plastic screws in the two left corners.
▶ Open the housing cover.
▶ Adjust the time switch in accordance with the illustration at the side:
▶ Select the desired operating times by tuning the running wheel. ➊
▶ Select the desired time slots by latching to the left. ➋
▶ Synchronise the current time at the triangle.
▶ Select operating mode (I = Continuous operation, = Time switch
operation, 0 = Permanently off).
▶ Check whether the desired operating mode has been selected.
L By sliding the latching piece to the left, a 15 minute time interval is set to „ON".
All of the latching pieces remaining in the right position are „OFF".
016-100_01
Installation and operating manual
1
4
5
Fig. [7]
2
3
55
Need help?
Do you have a question about the EasyClean SkimTech Basic and is the answer not in the manual?